Domestic Hot Water Distribution System Checklist

by Doug Page, PE, LEED AP

Design Phase

  • Explicitly document pipe design criteria.
  • Calculate flow rate using ASPE/ASHRAE-recommended protocol. If calculations are not performed, minimally use recommended heuristics for pipe sizing and loop flow rates.
  • Calculate system pressure drop for return and supply pipe, fittings, and valves. Contact heater manufacturer for published pressure drop. Size water circulator accordingly.
  • Ensure that the control sequence of the circulators meets the owner’s needs and is compatible with the system equipment, such as the heater and mixing valve.
  • Show balancing valves on domestic hot water return loops and pump discharge.
  • Show flow rates on drawings.
  • Explicitly specify balancing of the domestic water system.
  • Specify maximum lead content of balancing valves.
  • Show insulation on the supply and return piping.
  • Show air vents at the tops of risers.
  • Size expansion tanks.

 

Construction Phase

  • Verify general installation including pipe sizing, insulation thickness, integrity/continuity of insulation, balancing valve types and locations, air vent locations, and pipe supports.
  • Inspect for cross-connected water pipes during construction.
  • Flush (and disinfect) domestic system.
  • Field adjust shower mixing valves. Commission the master mixing valve.
  • Balance the distribution system. Review balancing report.
  • Adjust air pressure in expansion tanks.
  • In a commercial kitchen, verify maximum time for hot water with appropriate jurisdiction (e.g., local health department and/or U.S. Department of Agriculture).